Elbow Flashover
Summary
There is a need for the industry to track the performance of separable connector
systems (elbows, caps, and bushings) with regard to flashovers
during light-load and
no-load conditions. A web-based database has been established by DSTAR, and is open for
industry-wide input. Results will also be made available to the industry.
Problem Background
There have been widespread reports
in the industry of flashovers during operation of elbows and insulated bushing caps. These
failures have occurred primarily during routine switching when very small load currents,
or just cable charging current, are interrupted. The numerous flashovers during insulated
cap removal have been particularly perplexing because virtually no current is interrupted.
In general, these flashovers
are much more frequent at the higher distribution voltages; 25 and 35 kV. Flashovers have
been reported involving products from all of the major manufacturers.
These elbow and insulated cap flashovers are of
particular concern due to the proximity of operating personnel to the faults. In addition,
customer interruptions, material replacement costs, and lost crew time are additional
negative consequences of these flashovers.
IEEE Standard 386 calls for elbows and bushings to
be tested for their ability to safely interrupt load currents up to their rating. Present
standards, however, do not address the performance under low-load or no-load conditions.
Industry Response
The Distribution Systems
Testing, Application, and Research (DSTAR) group began an extensive series of
investigations and tests in 1995 to determine the causes for these flashovers. In
addition, the Insulated Conductors Committee of the IEEE Power Engineering Society also
has been considering standards revisions.
Spurred by the concerns of the utility industry, the
major manufacturers of these components have also performed their own investigations.
Removal of an elbow or cap expands the sealed air
volume inside the elbow, creating a partial vacuum. This is illustrated in Figure 2.
According to Paschens Law, partial vacuum reduces the dielectric strength of the
air. The consensus within the industry is that this partial vacuum is a significant cause
for the flashovers. In response, major manufacturers have introduced re-designed
components which seek to mitigate the partial vacuum condition.
During the DSTAR investigations, flashovers occurred for which the
partial vacuum theory may not provide a satisfactory explanation. Figure 1 shows video
frames from DSTAR tests. The first frame shows the elbow cuff clear of the bushing. By
this time, partial vacuum along the elbow/bushing interface should have been equalized. In
the next frame, a flashover occurs.
 
Figure 1
Click
here to see a short video of the above test.

Figure 2
|
|