Wye-Delta Overhead Banks

Switching overhead wye-delta three-phase transformer banks phase-by-phase can create overvoltage problems and fail arresters or transformers. This topic was investigated by DSTAR research, yielding guidelines on switching practices, overvoltage protection, and the capability of arresters to survive these overvoltages. This research has even discovered a previously unreported overvoltage phenomenon, creating extreme overvoltages magnitudes, which is the apparent cause for numerous transformer failures reported in the field.  An example of this newly discovered overvoltage phenomenon is shown below. 

sdni.jpg (42155 bytes)

Phase to ground voltage on a bank of  three 25 kVA low-loss poltop distribution transformers connected in wye-delta.  One phase was previously closed, the second primar phase was closed at 21 ms on the plot shown below

 